In TOP SECRET areas, the front covers for conduits and cable trays in floors, ceilings and of associated fittings MUST be clear plastic or be
inspectable and have tamper proof seals fitted.
10.4.7.C.02.
ControlSystem Classification(s): All Classifications; Compliance: SHOULD
[CID:2350]
The front covers of conduits, ducts and cable trays in floors, ceilings and of associated fittings SHOULD be clear plastic or be inspectable and
have tamper proof seals fitted.
10.4.8.
Cabling in walls or party walls
10.4.8.R.01.
Rationale
In a shared non-government facility, cabling run correctly in walls allows for neater installations facilitating separation and inspectability.
Controls are more stringent than in a non-shared facility or a shared government facility.
10.4.8.R.02.
Rationale
A party wall is a wall shared with an unclassified area where there is no control over access. In a shared non-government facility, cabling is not
allowed in a party wall. An inner wall can be used to run cabling where the area is sufficient for inspection of the cabling.
10.4.8.C.01.
ControlSystem Classification(s): Confidential, Secret, Top Secret; Compliance: MUST NOT
[CID:2354]
Cabling MUST NOT run in a party wall.
10.4.9.
Sealing reticulation systems
10.4.9.R.01.
Rationale
In a shared non-government facility, where the threats of access to cable reticulation systems is increased, GCSB endorsed anti-tamper seals
are required to provide evidence of any tampering or illicit access.
10.4.9.R.02.
Rationale
In a shared non-government facility, all conduit joints and wall penetrations are sealed with a visible smear of glue or sealant to prevent access
to cabling.
10.4.9.C.01.
ControlSystem Classification(s): Top Secret; Compliance: MUST
[CID:2358]
Agencies MUST use GCSB endorsed tamper evident seals to seal all removable covers on reticulation systems, including:
conduit inspection boxes;
outlet and junction boxes; and
T-pieces.
10.4.9.C.02.
ControlSystem Classification(s): Top Secret; Compliance: MUST
[CID:2359]
Tamper evident seals MUST be uniquely identifiable and a register kept of their unique number and location.
10.4.9.C.03.
ControlSystem Classification(s): Top Secret; Compliance: MUST
[CID:2360]
Conduit joints MUST be sealed with glue or sealant.
10.4.9.C.04.
ControlSystem Classification(s): All Classifications; Compliance: SHOULD
[CID:2361]
Conduit joints SHOULD be sealed with glue or sealant.
10.4.10. Wall penetrations
10.4.10.R.01. Rationale
A cable wall penetration into a lesser-classified area requires the integrity of the classified area be maintained. All cabling is encased in conduit
with no gaps in the wall around the conduit. This prevents any visual access to the secure area.
10.4.10.C.01. ControlSystem Classification(s): Confidential, Secret, Top Secret; Compliance: MUST
[CID:2365]
Wall penetrations that exit into a lower classified area, cabling MUST be encased in conduit with all gaps between the conduit and the wall filled
with an appropriate sealing compound.
10.4.11. Power reticulation
10.4.11.R.01. Rationale
In a shared non-government facility, it is important that TOP SECRET systems have control over the power system to prevent denial of service
by deliberate or accidental means. The addition of a UPS is required to maintain availability of the TOP SECRET systems.
10.4.11.C.01. ControlSystem Classification(s): Confidential, Secret, Top Secret; Compliance: MUST
[CID:2368]
Secure facilities MUST have a power distribution board located within the secure area and supply UPS power all equipment.
10.4.12. Power Filters
10.4.12.R.01. Rationale
Power filters are used to provide filtered (clean) power and reduce opportunity for technical attacks. Refer to10.1.32 or consult the GCSB for
technical advice.
10.4.12.C.01. ControlSystem Classification(s): Confidential, Secret, Top Secret; Compliance: MUST
[CID:2371]
Power filters MUST be used to provide filtered (clean) power and reduce opportunity for technical attacks.
10.4.13. Equipment Cabinet separation
104
Version_3.5__January-2022
Select target paragraph3
Connect to a paragraph
Connect to an entity
Disable highlights
Add to table of contents