10.6.5. For patch cables, the same connectors can be used for different classificationsif the length of the higher classified patch cables isless than the distance between the higher classified patch panel and any patch panel of a lower classification. Fibre optic patch panels 10.6.6. For Fibre optic patch panels are sometimes also described as fibre distribution panels. Their principal function is to safety terminate the fibre optic cable and provide connection access to the cable’s individual fibres. 10.6.7. Fibre patch panels are termination units, providing a secure, organised chamber for housing connectors and splice units while organising, managing and protecting fibre optic cable, splices and connectors. 10.6.8. Fibre patch panels can be either rack mounted or wall mounted and are usually placed near terminating equipment and connected with patch cables. Free standing patch panel racks are also available. Patch panels may also be mounted within standard equipment racks. 10.6.9. Rack mount panels may have flat or angled faces to assist in organising the cables themselves. Angled panels are intended to direct patch cables into vertical cable managers on either side of the rack. This facilitates maintenance and reduces the requirement for horizontal cable management. 10.6.10. Fibre patch panels can accommodate fibre adapter panels (also called connector panels), associated trunk cables, connectors, patch cords, and usually integrate cable management. 10.6.11. There are several components in a fibre patch panel which may include: Chassis or frame; Drawer to facilitate access for installation and maintenance; Cassette; Coupler panels (adapter panels) – to hold the connector couplers; The connector couplers (connector adapters); Splice tray – organises and secures splice modules; Patch cable management trays. 10.6.12. While well over 80 different fibre optic cable connector types have been manufactured, there are between 15 and 20 types in common use. Multimedia Patch Panels 10.6.13. A multimedia modular panel allows copper and fibre cables to be terminated in the same rack mount space. It accommodates several different adapters, suited for Cat6a/6/5e/5 Ethernet cables and fibre patch cables. Rack Layout and Cable Management 10.6.14. Standardised rack layouts and cable management are important for engineering support, security, equipment cooling and to minimise accidental or unnecessary outages. Many data centres will dictate a hotside (hot air out) and coldside (cold air in). The hotside is generally the rear of equipment and the rack. The coldside is generally the front panel of equipment and rack. The ducting of hot/cold air is often also standardised. 10.6.15. Standardising rack layout and cable management minimises problems caused by: Accidently not being able to locate end points of network and patch cables without tracing the cable end to end. Physically impeding access to equipment. Positioning of equipment and cables such that airflow (cooling) is impeded. As the density of equipment in racks increases, cooling becomes an increasingly important factor. Poor rack design combined with dense rack utilization can contribute to internal rack temperatures significantly higher than ambient room temperatures. 10.6.16. Standardising rack layout and cable management also assists in the maintenance of separation and segregation betweenRED/BLACK systems. Standardised Rack Configuration 10.6.17. Separate RED/BLACK racks are easier to manage, build and maintain and reduce the opportunity for accidental or deliberate cross-connection of RED/BLACK systems. Ideally separate RED/BLACK racks should be used. 10.6.18. In small installations (typically single workstation) shared racks are unavoidable. In such cases a shared rack configuration is permissibleprovided separation elements and controls are properly implemented. Extra care must be taken to avoid accidental cross-connection of systems. The following illustrates a standardised shared rack configuration where RED/BLACK and power systems are separated: 107 Version_3.5__January-2022

Select target paragraph3

Connect to a paragraph
Connect to an entity
Disable highlights
Add to table of contents