The labelling system, and the identifiers used, are agreed upon by all stakeholders; and
Labelling is all-encompassing and include cables, connecting hardware, conduits, firestops, grounding and bonding locations, racks,
cabinets, ports, and telecommunications spaces.
10.6.30.R.02. Rationale
Specific labelling requirements include:
All labels use a permanent identifier;
The labelling/numbering scheme is logical in its organisation, using alphanumeric characters for ease of reference;
Each cable and each pathway is labelled on each end, and each label identifies the termination points of both ends of the cable;
All labels are legible, defacement resistance, and have high adhesion characteristics and durability;
Labels are placed so they can be read without disconnecting a cable;
Labels for station connections may appear on the face plate;
All jack, connector, and block hardware are be labelled on either the outlet or panel; and
All labels match with the any installation and maintenance records.
10.6.30.C.01. ControlSystem Classification(s): Confidential, Secret, Top Secret; Compliance: SHOULD
[CID:5627]
Agencies SHOULD implement the principles and specific cable labelling requirements described above.
10.6.31. Power Cords
10.6.31.R.01. Rationale
It is important to separate copper data cables and power cables as all power feeds, line and connectors have the potential to emanate, create
magnetic fields and cause interference with copper data cables if laid in close proximity to each other. Good practice is to:
Label power cords at both ends to minimise the risk inadvertently disconnecting the wrong power cord;
Colour code power cords and power strips;
Use locking power cords, receptacles, or retention clips.
10.6.31.C.01. ControlSystem Classification(s): Confidential, Secret, Top Secret; Compliance: SHOULD
[CID:5619]
Agencies SHOULD follow best practice described above for the installation of power cables.
10.7. Emanation Security Threat Assessments
Objective
10.7.1. In order to minimise compromising emanations or the opportunity for a technical attack, a threat assessment is used to determine appropriate
countermeasures.
Context
Scope
10.7.2. This section relates to emanation security threat assessment advice and identification of appropriate countermeasures to minimise the loss of classified
information through compromising emanations or a technical attack.
10.7.3. This section is applicable to:
agencies located outside New Zealand;
secure facilities within New Zealand; and
mobile platforms and deployable assets that process classified information.
References
10.7.4. Information on conducting an emanation security threat assessment and additional information on cabling and separation standards, as well as the
potential dangers of operating RF transmitters in proximity to classified systems, is documented in:
Reference
NZCSS 400
Title
Installation Engineering
Publisher
Source
GCSB
CONFIDENTIAL document available
on application to authorised
personnel
NZCSI 403B
TEMPEST Threat and
GCSB
CONFIDENTIAL document available
Countermeasures Assessment
on application to authorised
personnel
NZCSI 420
Laboratory Tempest Test
GCSB
CONFIDENTIAL document available
Standard for Equipment in
on application to authorised
Controlled Environments
personnel
PSR references
10.7.5. Relevant PSR requirements can be found at:
Reference
112
Title
Source
Version_3.5__January-2022