Labelling conduits
Labels for TOP SECRET conduits should be of sufficient size and colour to allow for easy identification.
Security Control: ISM-0201; Revision: 3; Updated: Mar-21; Applicability: TS; Essential Eight: N/A
Labels for TOP SECRET conduits are a minimum size of 2.5 cm x 1 cm, attached at five-metre intervals and marked as ‘TS
RUN’.
Cables in walls
Cables run correctly in walls allow for neater installations while maintaining separation and inspection requirements.
Security Control: ISM-1115; Revision: 4; Updated: Dec-19; Applicability: All; Essential Eight: N/A
Cables from cable trays to wall outlet boxes are run in flexible or plastic conduit.
Cables in party walls
In shared facilities, TOP SECRET cables are not run in party walls. However, an inner wall can be used to run TOP SECRET
cables where sufficient space exists for their inspection.
Security Control: ISM-1133; Revision: 3; Updated: Dec-21; Applicability: TS; Essential Eight: N/A
In shared facilities, TOP SECRET cables are not run in party walls.
Wall penetrations
Penetrating a wall between a TOP SECRET area and a lower classified area requires the integrity of the TOP SECRET area
to be maintained. In such scenarios, TOP SECRET cables should be encased in conduit with all gaps between the TOP
SECRET conduit and the wall filled with an appropriate sealing compound.
Security Control: ISM-1122; Revision: 2; Updated: Dec-21; Applicability: TS; Essential Eight: N/A
Where wall penetrations exit a TOP SECRET area into a lower classified area, TOP SECRET cables are encased in conduit
with all gaps between the TOP SECRET conduit and the wall filled with an appropriate sealing compound.
Wall outlet boxes
Wall outlet boxes are the main method of connecting cabling infrastructure to workstations. They allow the
management of cables and the types of connectors allocated to various systems.
Security Control: ISM-1104; Revision: 4; Updated: Dec-21; Applicability: All; Essential Eight: N/A
Wall outlet boxes have connectors on opposite sides of the wall outlet box if the cable group contains cables belonging
to different systems.
Security Control: ISM-1105; Revision: 3; Updated: Mar-21; Applicability: All; Essential Eight: N/A
Different cables groups do not share a wall outlet box.
Labelling wall outlet boxes
Clear labelling of wall outlet boxes diminishes the possibility of incorrectly attaching ICT equipment to the wrong wall
outlet box. In cases were a wall outbox has a cable group containing cables belonging to different systems, each
connector should be individually labelled.
Security Control: ISM-1095; Revision: 5; Updated: Dec-21; Applicability: All; Essential Eight: N/A
Wall outlet boxes denote the systems, cable identifiers and wall outlet box identifier.