Recommended Control 01:
Recommended Control 02:
Recommended Control 03:
Recommended Control 04:
Recommended Control 05:
In a shared Non‐Government Facility agencies should use fiber
optic cabling
Cabling shouldbe inspectable at a minimum of five‐meter intervals
Flexible or plastic conduit should be used in walls to run cabling
from cable trays to wall outlets
The front covers of conduits, ducts and cable trays in floors,
ceilings and of associated fittings should be clear plastic or be
inspectable and have tamper proof seals fitted
Conduit joints should be sealed with glue or sealant
Fiber optic cabling is essential in a shared non‐government facility. Fiber optic cabling does not
produce and is not influenced by electromagnetic emanations; as such it offers the highest degree
of protection from electromagnetic emanation effects especially in a shared non‐government
facility where an agency’s controls may have a limited effect outside the agency controlled area.
Fiber optic cable is more difficult to tap than copper cabling and anti‐tampering monitoring can be
employed to detect tampering. Many more fibers can be run per cable diameter than wired cables,
reducing cable infrastructure costs.
In a shared non‐government facility, it is imperative that cabling systems be inspectable for
tampering and damage on a regular basis particularly where higher threat levels exist or where
threats are unknown.
In a shared non‐government facility, cabling run correctly in walls allows for neater installations
facilitating separation and inspectability. Controls are more stringent than in a non‐shared facility or
a shared government facility.
13.5.
Cable Labelling and Registration
Objective
Recommended Control 01:
Recommended Control 02:
Recommended Control 03:
Recommended Control 04:
6
To facilitate cable management, and identify unauthorized
additions or tampering
The SOPs6 should record the site conventions for labelling and
registration
Agencies should label cables at each end, with sufficient
information to enable the physical identification and inspection of
the cable
Agencies should maintain a register of cables
The cable register should record at least the following information:
SOP: Standard operating procedure
58